How it Works

The diagram below illustrates the HVAC operation using ventilation only and ventilation and scrubbing.

HLR_INDOOR_MODULES

HLR 15M and 14M Indoor Modules Have Four Integrated Capabilities

Indoor Air Scrubbing (Adsorption Mode)

A fraction of the return air stream is directed through the HLR 15M or 14M Module to remove indoor-generated contaminants using a blend of sorbents that capture carbon dioxide (CO2) along with a wide range of volatile organic compounds (VOCs), aldehydes, ozone, acids and particulate matter (PM2.5) resulting in cleaned air that flows back into circulation.

Outside Air Intake Reduction

Outside air reduction leads to lower cooling and heating energy consumption² and reduces the intake of outdoor generated pollutants. By following ASHRAE Standard 62.1 IAQP, HLR Technology enables significant outside air reduction relative to the typically prescribed amounts, while maintaining indoor air quality.

Automatic Self-Cleaning (Regeneration Mode)

The sorbents are designed to release captured contaminants upon heating. The HLR 15M and 14M Modules are equipped with a built-in heater and perform a periodic regeneration process to clean the sorbents and expel contaminants outside the building. Regeneration is managed for optimal performance and minimal energy use.

Monitoring and Reporting

HLR software communicates continuously with the onboard sensors to record, report and optimize all aspects of the HLR module’s operation. The system provides secure, real-time reporting of IAQ and operating parameters to the enVerid Cloud™

1 The mass balance analysis is performed per contaminant and per zone to ensure all contaminants are properly below their established limits. These “per zone” outside air CFMs are summed to yield the total ventilation required for the building. enVerid’s IAQP calculator makes it easy.

2 When economizer operation is favorable, outside air is increased and the HLR module is in standby.

What’s Inside the HLR 15M Indoor Module?

HLR 15M INDOOR MODULE

HLR 15M Indoor Module Adsorption & Regeneration Modes

The diagrams below depict the “under-the-hood” view of HLR 15M Module operation during the adsorption and regeneration modes.

HLR 15M INDOOR MODULE ABSORBTION & REGENERATION MODES

HLR 15M Indoor Module Drawings

HLM 15M INDOOR MODULE DRAWINGS - TOP VIEW
HLM 15M INDOOR MODULE DRAWINGS - SIDE VIEW

What’s Inside the HLR 14M Floor Module?

HLR_14M_INDOOR_MODULE_INSIDE

HLR 14M Floor Module Adsorption and Regeneration Modes

The diagrams below depict the “under-the-hood” HLR 14M Module operation during the adsorption and regeneration modes.

HLR_14M_INDOOR_MODULE_ABSORPTION_REGENERATION_MODES

HLR 14M Indoor Module Drawings

HLR 14M INDOOR MODULE DRAWINGS TOP VIEW
HLR 14M INDOOR MODULE DRAWINGS SIDE VIEW

HLR 15M and 14M Indoor Module Specifications

Installation Mechanical Room or Air Plenum
Construction
Sorbent Cartridges per Set 12
Typical Airflow (Adsorption) 700 - 800 SCFM 1,190 - 1,360 CMH
Typical Airflow (Regeneration) 250 – 300 SCFM 425 – 510 CMH
Static pressure added to AHU fan None
Sound Power Level 68 dB
Maximum Allowed External Static Pressure 0.2” WG/50 Pa
Maintenance Annual
Operating Life 20+ years with scheduled maintenance
Cellular Link 3G / 4G
BMS Integration BACnet over MSTP or Hardwire
POWER
Voltage (VAC) Frequency (Hz) MCA MOCP
208 V 60 Hz 34.3 Amp 35 Amp
277 V 60 Hz 30.6 Amp 35 Amp
240 V 50 Hz 28.4 Amp 30 Amp
SYSTEM POWER CONSUMPTION
208 V 277 V 240 V
Adsorption Mode 300 W 300 W 300 W
Regeneration Mode 5,800 W 6,800 W 5,540 W
REQUIRED CONTROL CONNECTIONS
Start/Stop Binary Input to HLR Module
OPTIONAL CONNECTIONS
Fire Signal Binary Input to HLR Module
HLR Status Analog Output from HLR Module
Regeneration Booster Fan Start/Stop Binary Output from HLR Module
Indoor Air CO2 Sensor Analog Output from HLR Module
Indoor Air TVOC Sensor Analog Output from HLR Module
HLR 15M MODULE WEIGHTS
Module Shipping Weight 600 lbs 272 kg
Cartridge Shipping Weight 200 lbs 91 kg
Installation/Operating Weight 630 lbs 286 kg
HLR 15M MODULE DIMENSIONS (Front View)
Height (Allow Additional 21” Clearance for Elbow) 75” / 1,905 mm
Width (Allow Additional 36” Clearance for Control Panel Service) 49” / 1,245 mm
Depth (Allow Additional 36” Clearance for Cartridge Service) 26” / 660 mm
Ducts (Indoor Air Inlet and Clean Air Outlet) 6.375” x 18” w/ 1.25” flange
162 mm x 406 mm w/ 32 mm flange
Ducts(Exhaust Air Outlet) 6.375” x 16” w/ 1.25” flange
162 mm x 406 mm w/ 32 mm flange
HLR 14M MODULE WEIGHTS
Module Shipping Weight 650 lbs 295 kg
Cartridge Shipping Weight 200 lbs 91 kg
Installation/Operating Weight 630 lbs 286 kg
HLR 14M MODULE WEIGHTS (Front View)
Height (Allow Additional 21” Clearance for Elbow) 72” / 1,829 mm
Width (Allow Additional 36” Clearance for Control Panel Service) 48” / 1,219 mm
Depth (Allow Additional 36” Clearance for Cartridge Service) 27” / 686 mm
Ducts (Indoor Air Inlet and Regeneration Air Inlet) 10” x 14” w/ 1.0” flange
254 mm x 356 mm w/ 25 mm flange
Ducts (Clean Air Outlet and Regeneration Exhaust) 10” x 14” w/ 1.0” flange
254 mm x 356 mm w/ 25 mm flange